Dynamic building simulations
Precise heating and cooling load calculations for informed investment decisions
We use our 3D model to simulate the actual energy performance of your buildings. This provides a reliable basis for correctly dimensioning systems, reducing operating costs, and better planning renovation measures.

Scope of service
Dynamic simulation
Simulation of heating or cooling requirements in accordance with SIA 380/2
Eegulatory strategies
Analysis of different control strategies and usage profiles
Scenario comparisons
Renovation measures and climate change can be taken into account
Room-by-room evaluation
Detailed simulation results per room zone
Why this is important
Your benefits
Ensure efficiency
Realistic simulations prevent oversized systems and unnecessary investments.
Reduce operating costs
Optimized systems reduce energy consumption and maintenance costs and extend the service life of your equipment.
Fast return on investment
Savings from optimized dimensioning and lower operating costs often exceed the analysis costs in the first year.
Gain planning reliability
Comparisons under different climate conditions and usage scenarios enable reliable decisions to be made.ermöglichen verlässliche Entscheidungen.
Creating transparency
All results are presented in a clear and comprehensible manner and can be accessed directly in NORM Explorer.
Practical examples

Efficient renovation of an office building in Zurich
During the renovation of an office building in Zurich, a detailed simulation enabled the heating load to be reduced from 460 kW to 360 kW. The analysis made it possible to use a smaller heat pump and significantly lower investment costs.
Initial situation
Heating load 460 kW
Simulation with NORM 3D model
Actual demand 360 kW
Result

Optimized connection power for a logistics center
A dynamic simulation showed that the originally estimated heating capacity of the logistics center was significantly too high. Thanks to the precise determination of requirements, the connected load could be reduced considerably.
Initial situation
District heating connection planned with 510 kW (existing value of the old system)
Simulation with NORM 3D model
Actual demand: 300 kW
Result